CALCULATION OF THE GEOMAGNETIC INDUCED CURRENTS IMPACT ON THE HIGH-POWER TRANSFORMER

Authors

DOI:

https://doi.org/10.15588/1607-6761-2019-4-1

Keywords:

transformers, geomagnetic induced currents, losses, temperature rises, calculations

Abstract

Purpose. Determination of resistance of a powerful power transformer to the action of geomagnetic induced currents (GIC) and structural measures for its increase, if necessary.

Methodology. An analytical calculation of the magnetization current (MC) is applied, which under the action of geomagnetic induced currents is excited in addition to the rated current in the higher voltage winding. Analytical and numerical calculations of the magnetic field and the losses, and computational-empirical methods for estimation of the temperature rises are used.

Findings. For a five-core transformer with a power of 630 MVA under the GIC effect, the increased losses and heating of structural elements on the cores of the magnetic system, the tank, and the increased sound level are determined.

Originality. For the case of orthogonal property of the vectors of winding rated currents and the vectors of harmonic components of the peak unbalanced MC, the Joule losses are represented by the sum of the losses due to these currents using the increase factors for ohmic losses in non-magnetic and ferromagnetic structural parts, which depend on MC harmonic spectrum.

Practical value.  The stability of the transformer under test to the given level of GIS was confirmed, and structural measures for its increase were recommended. The tested methods can be used in the computational design, in the study of real cases of equipment operation.

Author Biographies

V. F. Ivankov, Head of Dpt. at «Zaporozhtransformator» PrJSC, Zaporizhzhia, Ukraine

Ph. D. in Engineering Science, Head of Dpt. at «Zaporozhtransformator» PrJSC, Zaporizhzhia, Ukraine

A. V. Basova, Senior Engineer at «Zaporozhtransformator» PrJSC, Zaporizhzhia

Ph. D. in Engineering Science, Senior Engineer at «Zaporozhtransformator» PrJSC, Zaporizhzhia, Ukraine

References

[1] IEC 60076-7. (2018). Power transformers - Part 7: Loading guide for mineral-oil-immersed power transformers, 89.

[2] Bolduc, L., Aubin, J.. (1977/1978). Effect of direct currents in power transformers. Part I. A general theoretical approach. Electric Power Systems Research, 1, 291-298.

[3] Bolduc, L., Aubin, J.. (1977/1978) Effect of direct currents in power transformers. Part II. Simplified calculations for large transformers. Electric Power Systems Research, 1, 299-304.

[4] Chistiakov, H.N., Sihaev, S.N. (2011). Eksperimentalnoe issledovanie toka v neitrali transformatora v period heomahnitnykh bur. [Experimental study of the current in the neutral of the transformer during the period of geomagnetic storms]. News Tomsk Polytechnic University. Tomsk: State University, 318, 4, 122-127, (in Russian). Available: https://core.ac.uk/download/pdf/ 53067812.pdf.

[5] Effects of Geomagnetic Disturbances on the Bulk Power System. (2012). GMDTF Interim report: Norton American Electric Reliability Corporation, 137. Available: https://www.eenews.net/assets/2012/02/ 29/document_pm_01.pdf.

[6] Gigris, R., Vedante, K., Gramm, K. (2012). Effects of Geomagnetically Induced on Power Transformers and Power Systems. CIGRE, Report A2-304, 8.

[7] Hershenhorn, A.I. (1993). Vozdeistviia heomah-nitnykh tokov na elektrooborudovanie enerhosistem. [The effects of geomagnetic currents on electrical equipment of electrical energy systems]. Electric stations, 6, 54-63, (in Russian).

[8] Hurlet, P., Bertherau, F. (2007). Impact of geomagnetic induced currents on power transformer design. IEEE Conference MATPOST’07 - LYON, JST Transformateurs, France, 4.

[9] Klement, F., Leber, G. (2013). Designing for GIC withstand. Siemens: The Winning Transformers Indaba, 5-6 March, 1-21.

[10] Marketos, P., Moses, A.J., Hall, J.P. (2010). Effect of DC voltage on AC magnetization of transformer core steel. Journal of Electrical Engineering. 61, 7/s,. 123-125. Available: http://iris.elf.stuba.sk/JEEEC/ data/pdf/7s_110-34.pdf.

[11] Mousavi, S. A. (2012). Electromagnetic Modelling of Power Transformers with DC Magnetization. Sweden, Stockholm: Royal Institute of Technology (KTH), 86. ISBN 978-91-7501-537-8.

[12] Ngnegueu, T., Marketos, F., Devaux, F., Xu, T., Bardsley, R., Barker, S., Baldauf, J., Oliveira J. (2012). Behavior of transformers under DC/GIC excitation: Phenomenon, Impact on design/design evaluation process and Modelling aspects in support of Design. CIGRE, Report A2-303, 10.

[13] Passath, H., Leber, G., Hamberger, P., Bachinger , F. (2014). Direct current compensation – field experience under service conditions. Journal of Energy, vol. 63, Special Issue, 3-12. Available: http://www.hro-cigre.hr/downloads/casopis energija/ Journal of Energy_2014.pdf.

[14] Price, P. R. (2002). Geomagnetically induced current effects on transformers. IEEE Transaction on Power Delivery, 17, 4, 1002-1008. DOI: 10.1109/TPWRD. 2002.803710.

[15] Vakhnina, V.V., et al. (2018). Mekhanizmy voz-deystviya kvazipostoyannykh tokov na elektri-cheskiye seti: monografiya. [Mechanisms of the impact of quasi-constant currents on electrical networks: a monograph] M.: Infra-Inzheneriya, 256, (in Russian). Available: https://books.google.com.ua/ books?isbn=5041293384.

[16] Zirka, S.E., Moroz, Y.I., Arturi, C.M., Bonnman, D. (2017). Topological transient models of three-phase five-core transformer. Electrical Engineering And Power Engineering, 2, 18-25. DOI 10.15588/1607-6761-2017-2-2.

[17] Leites, L.V. (1991). Elektromahnitnye raschety trans-formatorov i reaktorov. [Electromagnetic calculations of transformers and reactors]. Moskow: Enerhiia, 392, (in Russian).

[18] Biki, M.A. (2013). Proektirovanie silovykh trans-formatorov. Raschety osnovnykh parametrov. [Design of power transformers. Calculations of the main parameters]. Moskow: Znak, 612, (in Russian). ISBN 978-5-87789-070-1.

[19] Ivankov V.F., Basova A.V., Shulga N.V. (2014). Elektroteplovyye raschetnyye modeli elementov konstruktsii silovykh transformatorov. [Electric-heating calculation models of structural elements of transformer equipment]. Electrical Engineering And Power Engineering, 2, 41-53, (in Russian). Available: http://nbuv.gov.ua/UJRN/etee_2014_2_8.

[20] Іvankov, V.F., Basova, A.V., Khimiuk, І.V. (2017). Metody modeliuvannia transformatoriv ta reaktoriv. [Methods of modeling of transformers and reactors]. Kyiv.: Nash format, 490, (in Ukrainian). ISBN 978-966-02-8297-1. Available: http://www.ied.org.ua/ files/monograf2_2017.pdf.

[21] IEEE Std C57.163-2015. IEEE Guide for Establishing Power Transformer Capability while under Geomagnetic Disturbances. 38.

Downloads

Published

2019-12-31

How to Cite

Ivankov, V. F., & Basova, A. V. (2019). CALCULATION OF THE GEOMAGNETIC INDUCED CURRENTS IMPACT ON THE HIGH-POWER TRANSFORMER. Electrical Engineering and Power Engineering, 1(4), 8–20. https://doi.org/10.15588/1607-6761-2019-4-1